TECHNICAL SPECIFICATIONS FOR ELEVATOR BACKUP 3Ph to 3Ph – PowerOn ELOS

Model | MPS 20000 |
Rating | 20KVA |
AC INPUT | 415V + 15% -20% Single Phase Input |
Frequency | 50Hz ± 6% |
DC VOLTAGE | 240 VDC |
Charging Time | 12 Hours of 90% of full Capacity |
Charger Type | CVCC Internal Controlled Rectifier type |
INVERTER: | |
Technology | IGBT Double Conversion |
Output Voltage | 400 / 415V AC Three Phase |
Frequency | 50Hz ± 0.5Hz |
Waveform | PWM Sine wave |
Harmonic Distortion | Less than 3% on Linear load |
Inverter Efficiency | > 92% |
Power Factor | 0.8 |
Overload | 105% Continuous, 300% for 60 sec |
Crest Factor | 4:1 |
Phase Displacement | 1200 ± 10 |
Audible Noise | Less than 45 dB at 1 Meter |
METERING: | |
Microprocessor based Digital LCD Meter for | R,Y,B Output Voltages, Output currents & Frequency, DC Voltage , Battery and Load Percentage, Last 5 Backup time Storage with no. of Lift Operation per Backup. |
GENERAL: | |
Dimensions (LxWxH)mm | 1040 x 350 x 910 |
Operating temperature | 00C to 500C |
Humidity | Max 95%, Non-condensing |
PROTECTIONS : | |
Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage Input Under & Overvoltage, Single Phasing & Phase unbalance | |
INDICATIONS & ALARMS | |
a) Mains on | Indication |
b) Inverter on | Indication |
c) DC Low | Indication & Alarm |
f) Fault | Indication & Alarm |
g) Output Overload | Indication & Alarm |
CHANGEOVER | |
b) Static Switch(Optional) | Bi-directional |
* Specifications are subject to change without prior notice due to constant improvement in design & technology |